Voltage Drop Calculator

Single Phase · Three Phase · DC · Series Runs · Motor Starting

⚡ Voltage Drop Calculator
📊 Results
📋 Cable Size Comparison

All common cable sizes for your circuit. Blue row = minimum recommended size.

Cable VD (V) VD (%) Ampacity (A) Status
📐 Worked Examples
SINGLE PHASE AC

House circuit: 2.4kW air conditioner, 25m from switchboard

Scenario: A 2,400W split-system air conditioner is installed 25 metres from the main switchboard. Supply is 230V single phase. Cable is 2.5mm² copper TPS in conduit. Power factor 0.95.

Step 1 — Find current: I = P / (V × PF) = 2,400 / (230 × 0.95) = 10.98 A

Step 2 — Apply formula: VD = 2 × L × I × ρ / A = 2 × 25 × 10.98 × 0.0175 / 2.5

Step 3 — Calculate: VD = 2 × 25 × 10.98 × 0.007 = 3.84 V

Step 4 — Check %: VD% = 3.84 / 230 × 100 = 1.67%

✅ PASS — 1.67% is well within the AS/NZS 3000 limit of 5%. 2.5mm² is adequate.

THREE PHASE AC

Factory sub-board: 22kW motor, 80m cable run

Scenario: A 22kW three-phase motor is supplied from a sub-board 80 metres away. Supply is 400V three phase. Cable is 6mm² copper. Full load current is 40A. Power factor 0.86.

Step 1 — Formula for 3-phase: VD = √3 × L × I × ρ / A

Step 2 — Calculate: VD = 1.732 × 80 × 40 × 0.0175 / 6 = 16.13 V

Step 3 — Check %: VD% = 16.13 / 400 × 100 = 4.03%

⚠️ BORDERLINE — 4.03% is within 5% but tight. Consider upgrading to 10mm² (VD = 2.42%) for any future load growth.

DC CIRCUIT

Solar battery system: 48V DC, 60A, 12m cable run

Scenario: A 48V DC solar battery system feeds an inverter 12 metres away. The battery cable carries 60A and is 16mm² copper. Maximum allowable voltage drop is 3%.

Step 1 — DC uses same formula as single phase: VD = 2 × L × I × ρ / A

Step 2 — Calculate: VD = 2 × 12 × 60 × 0.0175 / 16 = 1.58 V

Step 3 — Check %: VD% = 1.58 / 48 × 100 = 3.28%

⚠️ SLIGHTLY OVER 3% — Upgrade to 25mm² (VD = 1.01V, 2.10%) to meet the 3% design limit.

MOTOR STARTING

DOL motor start: 15kW, checking inrush voltage drop

Scenario: A 15kW DOL motor (full load current 28A) starts on a 400V three-phase circuit. Cable is 6mm² copper, 30m long. DOL starting current is 7× FLC = 196A. Max allowable starting VD is 15%.

Normal running VD: VD = 1.732 × 30 × 28 × 0.0175 / 6 = 4.24 V (1.06%)

Starting VD (196A): VD = 1.732 × 30 × 196 × 0.0175 / 6 = 29.7 V (7.42%)

Check ampacity: 6mm² copper rated approx. 38A — adequate for 28A FLC with 1.35× headroom.

✅ PASS — 7.42% starting VD is within the 15% limit. However, check that other sensitive equipment on the same supply is not affected by the momentary dip.

❓ Frequently Asked Questions
What is voltage drop?
Voltage drop is the reduction in voltage that occurs as electrical current flows through a conductor. Every cable has resistance, and when current flows through that resistance, some voltage is lost as heat. The greater the current, the longer the cable run, and the smaller the cable cross-section, the more voltage is lost. Excessive voltage drop causes equipment to run below its rated voltage, which can shorten equipment life and increase energy consumption.
What is the maximum allowed voltage drop in Australia?
Under AS/NZS 3000 (Australian Wiring Rules), the maximum allowable voltage drop from the point of supply to any point in the installation is 5% of the nominal supply voltage. For a 230V single phase circuit, that is 11.5V. For a 400V three phase circuit, that is 20V. Many designers aim for 3% or less for longer runs or sensitive equipment. Always check the equipment manufacturer's specifications as some equipment (particularly VFDs and UPS systems) specify tighter limits.
How do I calculate voltage drop?
Single Phase AC and DC: VD = 2 × L × I × ρ / A

Three Phase AC: VD = √3 × L × I × ρ / A

Where: L = one-way cable length (metres), I = current (amps), ρ = resistivity (0.0175 Ω·mm²/m for copper, 0.028 for aluminium), A = cable cross-sectional area (mm²). The factor of 2 in single phase accounts for the active and neutral conductors — current travels down and back. In three phase, √3 (≈1.732) is used instead because the three phases partially cancel each other out.
Why does voltage drop matter for motors?
Motors are particularly sensitive to voltage drop because motor torque varies with the square of voltage. A 10% voltage drop causes approximately 19% reduction in starting torque. This can cause motors to fail to start under load, stall during operation, or draw excessive current leading to overheating. AS/NZS 3000 requires voltage drop during motor starting to not cause malfunction of other connected equipment — typically limiting starting VD to 10–15%.
What is the difference between copper and aluminium cable voltage drop?
Copper has a resistivity (ρ) of 0.0175 Ω·mm²/m while aluminium has ρ = 0.028 Ω·mm²/m — about 60% higher. This means aluminium produces about 60% more voltage drop than copper of the same cross-section. To match a copper cable's voltage drop, aluminium needs to be approximately 1.6× the cross-section. However, aluminium is cheaper and lighter, making it preferred for large service mains and overhead lines.
What is ampacity and why does it matter?
Ampacity (current-carrying capacity) is the maximum continuous current a cable can carry without overheating. It is determined by the cable's cross-section, insulation rating, installation method (in conduit, clipped, buried etc.) and ambient temperature. A cable must be sized for BOTH adequate ampacity (to carry the current safely) AND acceptable voltage drop (to deliver the correct voltage). Often voltage drop is the more limiting factor for long cable runs.
What voltage drop limits apply in the United States (NEC)?
The National Electrical Code (NEC) does not mandate a specific voltage drop limit, but NEC 210.19(A) and 215.2(A) include informational notes recommending that voltage drop not exceed 3% for branch circuits and 5% total from service to outlet. Many utility companies and designers use 3% as a practical limit. US circuits typically use 120V (single phase, two-wire) or 240V (split-phase) for residential and 208V or 480V for commercial/industrial three-phase.
What does "one-way length" mean in voltage drop calculations?
One-way length is the distance from the supply point to the load — i.e., the length of cable from the switchboard or distribution board to the socket outlet, light fitting, or piece of equipment. The voltage drop formula multiplies this by 2 (for single phase/DC) because current must travel TO the load and then RETURN via the neutral or negative conductor. Always measure the actual cable route length, not the straight-line distance.

What Is Voltage Drop? A Complete Guide for Electricians and Engineers

Voltage drop is one of the most fundamental concepts in electrical installation design. Whether you're wiring a house, sizing cables for an industrial motor, or designing a solar battery system, understanding and calculating voltage drop correctly is essential for safe and compliant electrical installations.

The Physics of Voltage Drop

Every conductor — whether copper or aluminium — has electrical resistance. When current flows through a resistance, energy is lost as heat, and the voltage at the far end of the cable is lower than at the source. This reduction in voltage is what we call voltage drop.

The relationship is described by Ohm's Law: V = I × R, where V is the voltage drop in volts, I is the current in amps, and R is the total resistance of the cable in ohms. For a two-wire circuit (active and neutral, or positive and negative), the total resistance is twice the resistance of a single conductor, which is why the factor of 2 appears in the standard formula.

Single Phase AC / DC: VD = 2 × L × I × ρ / A
Three Phase AC: VD = √3 × L × I × ρ / A

Resistivity Values

MaterialResistivity ρ (Ω·mm²/m)Relative to Copper
Copper0.01751.0×
Aluminium0.0281.6×
Gold0.0221.26×
Silver0.0160.91× (better, but too expensive)

Australian Standards for Voltage Drop

In Australia, voltage drop limits are governed by AS/NZS 3000:2018 (Wiring Rules), which specifies that the voltage drop from the point of supply to any point in the installation shall not exceed 5% of the nominal supply voltage.

  • 230V single phase: maximum 11.5V drop
  • 400V three phase: maximum 20V drop
  • Extra-low voltage (ELV) circuits (e.g. 12V, 24V): often limited to 5% which is just 0.6V or 1.2V — making cable sizing critical

Many designers work to a tighter 3% limit to allow for future load growth and to account for the fact that supply voltage itself may vary ±6% from nominal. Some sensitive equipment such as variable frequency drives (VFDs) and medical equipment specify even tighter voltage tolerance.

Factors Affecting Voltage Drop

Four variables determine voltage drop: current (I), length (L), cable cross-section (A), and resistivity (ρ). Of these, the designer typically controls cable size and routing. To reduce voltage drop, you can:

  • Increase cable size — doubling the cross-section halves the voltage drop
  • Reduce cable length — move the distribution board closer to the load where possible
  • Reduce load current — improve power factor or reduce the load
  • Use copper instead of aluminium — copper has 37.5% lower resistivity
  • Run parallel cables — two cables in parallel halve the effective resistance

Voltage Drop vs. Ampacity — Two Separate Checks

A common mistake is to think that a cable sized for ampacity is automatically adequate for voltage drop. This is not always the case. For long cable runs — particularly in industrial, agricultural and rural settings — voltage drop is often the more limiting factor than ampacity. It is essential to check both:

  • Ampacity check: Can the cable carry the load current without overheating?
  • Voltage drop check: Is the voltage at the load end within the allowable limit?

Take the larger cable size from both checks.

Motor Starting Voltage Drop

Electric motors draw a large inrush current when they start — typically 5 to 7 times their full load current for direct-on-line (DOL) starters. This inrush lasts for 2–10 seconds and causes a momentary voltage dip on the supply. The voltage drop during starting must be checked separately from running voltage drop, as the currents involved are much larger.

Starting methods and their typical current multipliers:

Starting MethodStarting Current (× FLC)Notes
Direct-on-line (DOL)6–7×Highest inrush, simplest control
Star-Delta2–3×Reduces starting torque too
Soft Starter2–4×Programmable ramp time
Variable Frequency Drive (VFD)1–1.5×Best control, highest cost
Autotransformer2–4×Used for large motors

Voltage Drop in DC and ELV Systems

DC systems — including solar battery installations, EV charging systems, 12V/24V lighting, and telecommunications — can be particularly susceptible to voltage drop because the system voltage is low. A 1.2V drop on a 230V circuit is just 0.5%, but on a 12V circuit it is 10% — significant enough to cause LED lights to flicker, solar charge controllers to malfunction, or battery charging to be incomplete.

For 12V and 24V systems, it is common to design for a maximum of 2–3% voltage drop, requiring substantial cable cross-sections for high-current loads over any meaningful distance.

International Standards Summary

RegionStandardMax VD (typical)
Australia / New ZealandAS/NZS 30005%
United StatesNEC (informational note)3% branch, 5% total
IndiaIS 7325% (lighting 3%)
South AfricaSANS 101425%
United KingdomBS 76713% (lighting), 5% (other)
EuropeIEC 60364-5-523% (lighting), 5% (other)

📏 AS/NZS 3000 Reference

AS/NZS 3000

Maximum allowable voltage drop from point of supply to any point in installation: 5% of nominal voltage.

  • 230V single phase: max 11.5 V
  • 400V three phase: max 20 V
  • Many designers target ≤3% for sensitive loads
  • ELV systems: check equipment specs

📐 Cable Reference (mm²)

SizeAmpacity (A)

Approximate values for copper in conduit, 75°C. Apply derating factors per AS/NZS 3008 for installation conditions.

🛒 Buy Cable Online

⚡ Formula Quick Reference

Single Phase / DC:

VD = 2 × L × I × ρ / A

Three Phase:

VD = √3 × L × I × ρ / A

ρ (copper) = 0.0175 Ω·mm²/m

ρ (aluminium) = 0.028 Ω·mm²/m

√3 = 1.732